UPS battery pack isolation discharge test, UPS battery discharge process. The UPS battery pack offline charge and discharge test system includes a UPS power supply, a battery pack to be tested electrically connected to the UPS power supply, and a debugging device connected to the UPS power supply.
UPS battery pack isolation discharge test, UPS battery discharge process. The UPS battery pack offline charge and discharge test system includes a UPS power supply, a battery pack to be tested electrically connected to the UPS power supply, and a debugging device connected to the UPS power supply. In battery testing, the discharge method is a commonly used method. . The test interval is generally once a year to verify the capacity of the UPS battery pack.
UPS battery pack isolation discharge test method
1. First, check the UPS battery pack body and the switch instrument data on the power side and load side. If there is no abnormality, proceed to the next step;
2. Place the dummy load in a well-ventilated and safe location in the corridor, and connect the backup cable to the dummy load (a DC 4P400A circuit breaker is set in the middle of the wiring cable, and the switch is in the off position) for backup;
Low temperature lithium iron phosphate battery 3.2V 20A -20℃ charging, -40℃ 3C discharge capacity ≥70%
Charging temperature: -20~45℃ -Discharge temperature: -40~+55℃ -40℃ Support maximum discharge rate: 3C -40℃ 3C discharge capacity retention rate ≥70%
Click for details
3. Connect the dummy load control power supply to the backup switch of the corresponding voltage level for backup;
4. Confirm with the monitoring personnel through intercom, turn off the UPS battery pack switch, and prepare for wiring; the battery pack side is wired according to the planned wiring method and voltage level. The wiring personnel should wear insulating gloves and use insulating tools to remove the copper connecting bars of No. 96 and No. 97 batteries in the battery pack. Connect the cable (120mm) connected to the dummy load phase line firmly to the positive terminal of the UPS battery pack and to the dummy load neutral line. Connect the temporary wire to the negative terminal of the battery pack for later use.
5. Turn on the UPS battery group monitoring equipment and start monitoring the data of each battery to be tested;
6. Power on the dummy load control loop and turn on the dummy load; close the switch in the middle of the temporary battery test line and use a multimeter to test whether the voltage at both ends of the switch is consistent with the battery pack voltage (-216V);
7. Turn on the false load test mode: select the load switch test with the corresponding power level (a smaller power should be selected at the beginning), and use a clamp ammeter to detect the test current carried by the cable in real time (overload testing is not allowed).
Low temperature and high energy density 18650 3350mAh-40℃ 0.5C discharge capacity ≥60%
Charging temperature: 0~45℃ Discharge temperature: -40~+55℃ Specific energy: 240Wh/kg -40℃ Discharge capacity retention rate: 0.5C Discharge capacity ≥ 60%
Click for details
8. Through the test, observe the voltage drop of each battery in the UPS battery pack to see if any individual battery has a large voltage drop. Also check the appearance of each battery. The test current should not exceed the battery pack C10 discharge current. The test time should be combined with the on-site battery pack voltage drop. The single cell voltage should not be less than 1.85V.
9. After the test, restore the UPS battery pack wiring and switch status.
UPS battery discharge process
1. Set or calculate the UPS battery discharge time: Calculate the standby time based on the LCD panel display time or the number of batteries, and set the power outage time to 30% or 25% of the calculated time.
2. Directly turn off the "rectifier input switch" of the UPS and observe that the UPS LCD panel displays the remaining time and battery voltage, or that the number of indicator lights on the UPS front panel is not less than half of the original number of lights.
3. When the UPS battery is discharged to the battery low voltage alarm value, or the time reaches the previously budgeted time, close the "rectifier input switch" of the UPS.
Summary: The above is the isolation and discharge test of the UPS battery pack, the UPS battery discharge process, grasp the operation status of the UPS equipment in the station, troubleshooting, bottom-up, charge and discharge test of the battery pack, identify damaged and failed single-bottle batteries, and restore the overall performance of the battery pack , it is very necessary to ensure that the UPS system is working properly.
Popular recommendation
18650 battery flat top.What are the advantages of 18650 lithium battery?
2023-10-1318650 li ion battery.What is the production process of ternary cathode materials for lithium-ion bat
2023-10-083.7v 3000mah 18650 battery.Italy has developed a semi-solid lithium-oxygen battery that can be "
2023-10-081.5v Alkaline battery.What is the production process of 18650 lithium battery?
2023-10-09AG5 battery.One article tells you the key points of the 18650 lithium battery pack process
2023-10-091.5v Carbon battery.An alkaline battery charger circuit diagram
2023-10-09aaa battery alkaline!Graphene aerogel may help promote the development of lithium-sulfur batteries
2023-10-08803040 lipo battery.This article tells you what are the key points of the 18650 lithium battery pack
2023-10-09CR2450 battery.Commonly used filament preheating circuits for fluorescent lamps
2023-10-08alkaline battery!New energy battery technology solid state battery
2023-10-08LR621 battery!What is the impact of the battery management system?
2023-10-08AG11 battery!The key to developing energy storage lies in the advancement of battery technology
2023-10-08